AUDALRMAllows the monitor’s internal audible alarm to be
associated with any function of the monitoring system. Factory default is
OFF. Use the Keypad to select the desired audible alarm function, and
then press ENTER to save that value and return to the previous screen.
Audible Alarm Settings: OFF, ANY ALARM, SYSTEM FAULT, LEAK ALARM,
SPILL ALARM, EVAC ALARM, MONITOR STOPPED
NOTE: MONITOR STOPPED indicates there is a critical system fault, and the
monitor is no longer functioning correctly.
CLOCK – Sets the monitor’s date and time. Use the Keypad to enter
the correct date and time, and then press ENTER to save those values
and return to the previous screen. Note that time is displayed in a
24 hour format, while the date is displayed as mm/dd/yy.
SILENCE – Used to enter a length of time for which the internal
audible alarm and the external alarm are turned OFF when the front
panel SILENCE button is pressed. The factory default is 300 seconds
(5 minutes). If the cause of the alarm/fault has not been cleared at the
end of this time period, the internal audible alarm and the external alarm
device are reactivated. Use the Keypad to enter the desired time period,
and then press ENTER to save that value and return to the previous
screen.
SQUELCH – Sets a value of between 0.0 and 99.9 ppm that prevents
the display of measurements below that value. Factory default is 0 ppm.
For example, if the squelch setting is set to 50 ppm, then the monitor will
not display measurements that are below that value. Use the Keypad to
enter the desired value, and then press ENTER to save that value and
return to the previous screen.
ZONETEMP – Used to enter the temperature of the area being
monitored in °C, thus giving a more accurate ppm reading. The factory
default is 25°C. Use the Keypad to enter the desired temperature, and
then press ENTER to save that value and return to the previous screen.
CAL – Used to change a calibration factor for a specific gas. This
function is to be used ONLY with instructions from a Bacharach Service
Center. Factory default is 1.000.
P-CHK – This Pressure Check function displays the current manifold
pressure and the stored ambient pressure in psia, along with the difference
between these two pressures and the current fault code. Refer to
Working
with the P-CHK Function (Page
22).
CUST K1, K2 & K3 – Used to enter custom calibration data for a blend
of refrigerant gases that is not part of the monitor’s standard 24 refrigerant
gas library. Before using this function, the operator must contact the
factory and provide information about the blend of refrigerant gases to be
monitored. Custom calibration data will then be supplied to enable the
HGMSZ to accurately monitor that particular gas blend. To enter this data,
refer to Section
Entering Custom Refrigerant Calibration Values (Page 20).
A
UDIBLE ALARM IS
OFF
SET DATE & TIME
11/10/03 15:30
C
USTOM CAL K^1
xxxx.xxx
C
USTOM CAL K^2
yyyy
.
yyy
C
USTOM CAL K^3
zzzz.zzz
14.72 * AMB14.81
0.09dif <0000>
TEMP AT ZONE =
25 de
g
C
134A CALFACTOR
1.000
SILENCE TIMEOUT
0300 sec
SQUELCH BELOW
50.0
pp
m