Electrical Wiring
The HGM-SZ uses a universal power supply that is capable of accepting inputs of 100 to 240 VAC, 50/60 Hz.
The monitor’s power consumption is 15 Watts. It is highly recommended that the monitor be connected directly
to the AC power source, preferably on its own circuit. The connection should be completed with UL approved
multi-conductor wire (minimum 16 AWG), rated 300 VAC at 105°C.
Locate a convenient service knockout and install electrical conduit in the typical manner.
Locate the AC Input Terminals and Ground Stud on the inside of the monitor (Page 8).
Secure the incoming AC power neutral (white) and live (black) wires to the LINE 1 and LINE 2 terminals.
Using the supplied crimp-on ring terminals, washers, and nuts, connect the incoming AC power ground wire
(green) to the monitor’s AC Input Ground Stud, and then install a separate wire between the ground stud and
the GND terminal.
A switch or circuit breaker rated 1.0 A, 250 VAC, with a minimum terminal spacing of 3.0 mm must be attached
to the monitor’s AC power leads. This switch must also be located in close proximity to the monitor, and be in
easy reach of the operator. This switch should also be clearly marked as the monitor’s main AC disconnect
device.
AC Power Connections
WARNING: Electrical installation should be performed by a certified electrician, and
should comply with all applicable NEC/CEC and local electrical safety codes.
WARNING: The AC power ground wire must first be connected to the monitor’s ground
stud. Under no circumstances should this monitor be operated without a protective
ground. Doing so poses a potential shock hazard, and is also a violation of electrical
safety standards applicable to this type of equipment.
WARNING: Copper conductors for connection to supply mains must be made in
accordance with NEC/CEC and local codes
CAUTION: Drilling holes in the HGM-SZ enclosure may damage the unit and will void the
warranty. Please use knockouts provided for electrical connections.